| TYPE |
Portable, Lightweight, Automatic, 3-Phase Transformer Turns-Ratio Meter |
| PHYSICAL SPECIFICATIONS |
19”L x 15”W x 7”H (48.2cm x 38.1 cm x 17.8 cm); Weight: 25 lbs (11.3 kg) |
| INPUT POWER |
3 amps, 85-264Vac or 110-370 Vdc or 12Vdc |
| BATTERIES |
Two 12Vdc/2AH, Lead Acid Batteries (up to 3-hours operation) |
| MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
| RATIO-MEASURING RANGE |
0.8 to 15,000 (5-digit Resolution) |
| TURNS-RATIO ACCURACY |
0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.25%, 4,000 – 15,000: ±1% @ 8Vac
0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.20%, 4,000 – 15,000: ±1% @ 40Vac
0.8 – 1999: ±0.1%, 2,000 – 3,999: ±0.15%, 4,000 – 15,000: ±1% @ 100Vac |
| ADJUSTMENT |
None Required |
| TEST VOLTAGE |
8Vac @ 325 mA, 40 Vac @ 65 mA, 100Vac @ 26 mA |
| EXCITATION CURRENT READING RANGE |
0 to 2 Amperes |
| CURRENT READING ACCURACY |
±1mA, ±2% of Reading (±1 Digit) |
| PHASE-ANGLE MEASUREMENT |
0-360 Degrees |
| PHASE-ANGLE ACCURACY |
±0.2 Degree ( ±1 Digit) |
| DISPLAY |
LCD Screen: 20 Characters by 4 Lines; viewable in bright sunlight |
| PRINTER |
4.5-inch Thermal Printer |
| COMPUTER INTERFACE |
RS-232C, 19,200 Baud |
| PC SOFTWARE |
Windows 95/98/NT/2000/XP-based, included with purchase price |
| TEST RECORD STORAGE |
Stores 200 complete transformer test records. Each test record includes nameplate voltage, winding turns ratios, excitation current,
and winding phase angle. Data can be retained for two years. |
| TEST PLAN STORAGE |
Stores 128 transformer test plans |
| SAFETY |
Designed to meet UL 61010A-1 Certification and CAN/CSA C22.2 No. 1010.1-92 Certification |
| ENVIRONMENT |
Operating: -10° to 50° C (15° to +122° F); Storage: -30° C to 70° C (-22° to +158° F) |
| CABLES |
One 15’ single-phase cable set, One 15’ 3-phase cable set, One 25’ extension cable set
One cable-carrying duffel bag included |
| OPTIONS |
Transportation Case, Transformer Tap-Changer Remote Control Device |
| WARRANTY |
One-Year on Parts and Labor; Post Warranty Service Contract is Available |
|
 |