| TYPE |
Portable, Automatic, Single-Phase Transformer Turns-Ratio Tester |
| SIZE |
12 L by 8 W by 9 H inches |
| WEIGHT |
8 pounds |
| INPUT POWER |
120/240Vac (Selectable), 50/60Hz |
| MEASUREMENT METHOD |
ANSI/IEEE C57.12.90 |
| EXCITATION READING RANGE |
0 – 2 Amperes |
| RATIO-MEASURING RANGES |
0.8 to 15,000 (5-digit resolution) |
| TURNS-RATIO ACCURACY |
0.800–1,999 ±0.1 %,
2,000–3,999 ±0.25%,
4,000–15,000 ±1%
|
| CURRENT READING ACCURACY |
±1 Milliamp, ±2% of Reading (±1-digit) |
| ADJUSTMENT |
None required |
| TEST VOLTAGE |
8 Vac @ 1.0 Amp, 40 Vac @ 0.6 Amp |
| DISPLAY |
LCD Screen: 20 Characters wide by 4 Lines
Viewable in bright sunlight |
| COMPUTER INTERFACE |
RS-232C, 19,200 baud |
| IBM PC SOFTWARE |
Windows® 95/98/NT/2000/XP-Based, included with purchase price |
| SAFETY |
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 |
| ENVIRONMENT |
Operating: -10°C to 50°C (15°F to 122°F)
Storage: -30° C to 70°C (-22°F to 158°F) |
| CABLES |
One 15 ft. single-phase cable
One Cable-carrying Duffel Bag Included |
| OPTIONS |
Shipping Case |
| WARRANTY |
One-Year on Parts and Labor |
|
 |