| TYPE |
Portable Current-Transformer Test Set |
| PHYSICAL SPECIFICATIONS |
16"W by 11"H by 14"D (40.6 cm x 29.9 cm x 35.6 cm)
Weight: 40 lbs (20 Kg) |
| INPUT POWER |
90-130 Vac or 200-240 Vac, 50/60 Hz (user specified) |
| OUTPUT TEST VOLTAGE |
0 to 50 V ac @ 10A max
0 to 300 Vac @ 10A max
0 to 500 Vac @ 5A max
0 to 1200 Vac @ 2A max
0 to 2000 Vac @ 1.2A max |
| VOLTAGE READING RANGE |
0 to 2,200 Vac, Accuracy: ± 1.0% of reading, ± 1 volt |
| CURRENT READING RANGE |
0 to 10 A, Accuracy: ± 1.0% of reading, ± 0.02 A |
| TURNS-RATIO RANGE |
0.8 to 999, Accuracy: ± 0.1%
1000 to 1999, Accuracy: ± 0.3%
2,000 to 5,000, Accuracy: ± 1.0% |
| PHASE-ANGLE MEASUREMENT |
0 to 360 Degrees, Accuracy: ± 1.0 degree |
| DISPLAY |
LCD Screen: 20 characters by 4 lines; viewable in bright sunlight |
| PRINTER |
4.5-inch termal printer |
| COMPUTER INTERFACE |
RS-232C Port (115k baud) and one USB Port |
| PC SOFTWARE |
Windows® XP-based CT Analysis Program included with purchase price |
| TEST RECORD STORAGE |
Store 140 test records. Each test record may contain up to 10 sets of saturation, resistance and ratio data. |
| TEST PLAN STORAGE |
Store 128 test plans. Each test plan stores 10 saturation test voltage and current settings. |
| SAFETY |
Designed to meet UL 61010A-1 Certification and CAN/CSA C22.2 No. 1010.1-92 |
| ENVIRONMENT |
Operating: -10°C to 50°C (15° to +122° F)
Storage: -30° C to 70° C (-22° to +158° F) |
| CABLES |
Five 20' X cables set
One 35' H cable set
Power cord
One cable carrying duffel bag included |
| WARRANTY |
One-Year on Parts and Labor |
|
 |