| TYPE |
Microcomputer-driven EHV circuit-breaker analyzer |
| SIZE |
18" L x 15" W x 7" H (7.09 cm x 5.9 cm x 2.76 cm) |
| WEIGHT |
Less than 19 lbs (8.6 kg) |
| INPUT POWER |
3 amps, 90-130 Vac or 200-240 Vac, 50/60 Hz, selectable |
| TEMPERATURE |
Operating: -10ºC to 50ºC (15ºF to +122ºF)
Storage: -30ºC to 70ºC (-22ºF to +158ºF) |
| DRY CONTACT INPUT |
3 Dry-Input channels; Each channel detects Main and Insertion-Resistor Contacts |
| TIMING WINDOW |
Selectable: 1-second, 10-seconds, or 20-seconds |
| RESOLUTION |
± 100 microseconds at 1-second duration
± 1.00 milliseconds at 10-second duration
± 2.00 milliseconds at 20-second duration |
| ACCURACY |
0.05% of reading ±0.1 ms at 1-second duration |
DRY CONTACT
CHANNEL PROTECTION |
Fuses protect all isolated power supplies;
All contact inputs are grounded until test;
TVS and zener-diode protected |
| CONTACT DETECTION RANGE |
Closed: < 20 ohms
Open: > 5,000 ohms |
| RESISTOR DETECTION RANGE |
Range: 50 - 50,000 ohms |
| EXTERNAL TRIGGER INPUT |
Open/Close: 30-300V, dc or peak ac |
| VOLTAGE SENSING INPUT |
V1: analog input; 0-255, dc or peak ac, Sensitivity ±1V
V2: voltage detector (present/absent) input; 30-300V, dc or peak ac |
| INITIATE CURRENT SENSOR |
One, Non-contact, Hall-Effect sensor, 0-30-amp ranges, dc to 5Khz |
| BREAKER OPERATION |
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open |
| INITIATE CAPACITY |
25A/250Vac/dc max |
| TRAVEL TRANSDUCER INPUT |
1 digital travel transducer channel; Linear Range, 0.0-60.0 in (±0.005 in.); Rotary range: 0-360º (±0.006º) |
CONTACT TRAVEL
POINT DIFFERENCE |
Measures "Slow-close"contact-point distances (hard copy) |
BREAKER ANALYSIS
SOFTWARE |
Analysis software running under Windows 95/98/NT/2000 and features graphic display, numerical reports, and data base utility for use at shop or office. This software package is furnished with each Analyzer. |
| STORAGE CAPACITY |
Up to 200 timing shots, 45 breaker test plans |
| COMPUTER INTERFACE |
RS-232C |
| DISPLAY |
Back-lit LCD readout screen
20-character by 4-line display, viewable in bright sunlight |
| PRINTOUT |
Both graphic contact travel waveform and tabulated results are printed on 4.5 inch thermal paper |
| TRANSPORTATION CASE |
Hard case for shipping: available for both Travel Transducers and the VIC-DigiTimer |
| WARRANTY |
One year warranty on parts and labor
Post-warranty service contracts are available |