TYPE Special purpose test equipment, 600 ampere current source
PHYSICAL SPECIFICATIONS 16.8” W by 12.6” H by 10.6” D (42.6 cm x 32.0 cm x 27.0 cm)
Weight 46 lbs (21 kg)
INPUT POWER 90-130 Vac or 200-240 Vac (factory pre-set), 50/60 Hz
OUTPUT CURRENT 0 to 5 A @ 120 Vac max; 0 to 25 A @ 24 Vac max;
0 to 120 A @ 6 Vac max; 0 to 250 A @ 3 Vac max
INTERNAL CURRENT METER 100 mA to 1000 A; Accuracy: 1% of reading ±20mA;
MEASURING METHOD Isolated CT
EXTERNAL METER RANGE 10 mA to 10 A; Accuracy: 1% of reading, ±2 mA
TIMER READING RANGE 1ms to 2 hours, Accuracy: 0.1% of reading ±1ms
TIMER STOP INPUT Voltage input (24-300V, dc or peak AC);
or Dry Contact Input;
or removal of primary current
DISPLAY Backlit LCD, 4 lines by 20 characters
COMPUTER INTERFACE RS-232C (factory calibration and diagnostics)
SAFETY Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2
ENVIRONMENT Operating: -10°C to 50° C (15°F to +122° F)
Storage: -30° C to 70° C (-22°F to +158° F)
CABLES Power cord, Ground cable, 10 ft #2 AWG test leads
OPTIONS Shipping Case
WARRANTY One Year Parts & Labor, Post Warranty Service Contract Available