| TYPE |
Special purpose test equipment, portable circuit breaker analyzer |
| PHYSICAL SPECIFICATIONS |
16" W by 11" H by 14" D (40.6 cms x 29.9 cm x 35.6 cm)
Weight: 25 lbs (11.3 kg) |
| INPUT POWER |
90-130 Vac or 200-240 Vac (selectable), 50/60Hz |
| DRY-CONTACT INPUT |
3 or 6 dry-input channels; Each channel detects Main and Insertion-Resistor Contacts |
| TIMING WINDOWS |
Selectable: 1-second, 10-seconds or 20-seconds |
| TIMING RESOLUTION |
50 microseconds at 1-second duration;
0.5 milliseconds at 10-second duration;
1.00 milliseconds at 20-second duration |
| TIMING ACCURACY |
0.05% of reading, ±50 microseconds at 1-second duration |
| CONTACT DETECTION RANGE |
Closed: <20 ohms, Open:> 5,000 ohms |
| RESISTOR DETECTION RANGE |
50 – 5,000 Ohms |
| CT CURRENT SENSOR |
One, None Contacting, 0-150 Amp |
| EXTERNAL TRIGGER INPUT |
Open/Close: 30-300V dc or peak ac |
| VOLTAGE SENSING INPUT RANGE |
V1: analog input; 0–255 V, dc or peak ac
Sensitivity: ± 1 V; V2: voltage detector (present/absent)
input; 30-300V, dc or peak ac |
| BREAKER OPERATION |
Open, Close, Open-Close, Close-Open, Open-Close-Open |
| BREAKER INITIATE CAPACITY |
25 A/250 V ac/dc max (100A Inrush) |
| INITIATE CURRENT READING RANGE |
One, Non-contact, Hall-Effect sensor, 0-20-amp range, dc to 5 kHz |
| TRAVEL TRANSDUCER INPUT |
3 digital travel transducer channels; Linear range, 0.0-30.0 in (±0.01 in); Rotary range 0-360° (±0.36°) |
| CONTACT TRAVEL POINT DIFFERENCE |
Measures “Slow-Close” contact-point distances (hard copy printout) |
| DYNAMIC/STATIC RESISTANCE RANGE |
0.1 to 1,999 micro-ohm, Accuracy: ±2% of reading, ±5 micro-ohm |
| RESISTANCE TEST CURRENT |
200 Amperes Typical |
| RESISTOR TYPE TRANSUCER CHANNEL |
200 Ohm to 10 K Ohm |
| DISPLAY |
4 lines by 20 character back-lit LCD, sunlight viewable |
| PRINTOUT |
Both graphic contact-travel waveforms & tabulated results are printed on a 4.5-inch thermal printer |
| TEST RECORD STORAGE |
Store up to 100 timing records and 99 test plans |
| COMPUTER INTERFACE |
RS-232C port, USB Port |
| PC SOFTWARE |
Furnished Circuit breaker analysis software running under Windows XP; features graphic display,
numerical reports, and data base utility for use at shop or office. |
| SAFETY |
Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92 |
| ENVIRONMENT |
Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F) |
| OPTIONS |
Hard case for shipping; available for both Travel Transducers and CT-8000 |
| WARRANTY |
One-year warranty on parts and labor |