TYPE Special purpose test equipment, portable circuit breaker analyzer
PHYSICAL SPECIFICATIONS 16" W by 11" H by 14" D (40.6 cms x 29.9 cm x 35.6 cm)
Weight: 25 lbs (11.3 kg)
INPUT POWER 90-130 Vac or 200-240 Vac (selectable), 50/60Hz
DRY-CONTACT INPUT 3 or 6 dry-input channels; Each channel detects Main and Insertion-Resistor Contacts
TIMING WINDOWS Selectable: 1-second, 10-seconds or 20-seconds
TIMING RESOLUTION 50 microseconds at 1-second duration;
0.5 milliseconds at 10-second duration;
1.00 milliseconds at 20-second duration
TIMING ACCURACY 0.05% of reading, ±50 microseconds at 1-second duration
CONTACT DETECTION RANGE Closed: <20 ohms, Open:> 5,000 ohms
RESISTOR DETECTION RANGE 50 – 5,000 Ohms
CT CURRENT SENSOR One, None Contacting, 0-150 Amp
EXTERNAL TRIGGER INPUT Open/Close: 30-300V dc or peak ac
VOLTAGE SENSING INPUT RANGE V1: analog input; 0–255 V, dc or peak ac
Sensitivity: ± 1 V; V2: voltage detector (present/absent) input; 30-300V, dc or peak ac
BREAKER OPERATION Open, Close, Open-Close, Close-Open, Open-Close-Open
BREAKER INITIATE CAPACITY 25 A/250 V ac/dc max (100A Inrush)
INITIATE CURRENT READING RANGE One, Non-contact, Hall-Effect sensor, 0-20-amp range, dc to 5 kHz
TRAVEL TRANSDUCER INPUT 3 digital travel transducer channels; Linear range, 0.0-30.0 in (±0.01 in); Rotary range 0-360° (±0.36°)
CONTACT TRAVEL POINT DIFFERENCE Measures “Slow-Close” contact-point distances (hard copy printout)
DYNAMIC/STATIC RESISTANCE RANGE 0.1 to 1,999 micro-ohm, Accuracy: ±2% of reading, ±5 micro-ohm
RESISTANCE TEST CURRENT 200 Amperes Typical
RESISTOR TYPE TRANSUCER CHANNEL 200 Ohm to 10 K Ohm
DISPLAY 4 lines by 20 character back-lit LCD, sunlight viewable
PRINTOUT Both graphic contact-travel waveforms & tabulated results are printed on a 4.5-inch thermal printer
TEST RECORD STORAGE Store up to 100 timing records and 99 test plans
COMPUTER INTERFACE RS-232C port, USB Port
PC SOFTWARE Furnished Circuit breaker analysis software running under Windows XP; features graphic display,
numerical reports, and data base utility for use at shop or office.
SAFETY Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92
ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)
OPTIONS Hard case for shipping; available for both Travel Transducers and CT-8000
WARRANTY One-year warranty on parts and labor