| TYPE |
Special purpose test equipment, portable circuit breaker analyzer |
| PHYSICAL SPECIFICATIONS |
16” W by 11” H by 14” D (40.6 cm x 29.9 cm x 35.6 cm);
Weight, less than 25 lbs (11.3 kg) |
| INPUT POWER |
90-130 Vac or 200-240 Vac (selectable), 50/60Hz |
| DRY-CONTACT INPUTS |
3, 6 or 12 dry-input channels. Each channel detects Main and Insertion-Resistor Contacts |
| TIMING WINDOWS |
Selectable: 1-second, 10-seconds, 20-seconds |
| TIMING RESOLUTION |
±50 microseconds at 1-second duration ±500 microseconds at 10-second duration ±1.0 milliseconds at 20-second duration |
| TIMING ACCURACY |
0.05% of reading, ±0.05 ms at 1-second duration |
DRY CONTACT
CHANNEL PROTECTION |
Fuses protect all isolated power supplies. All contact inputs are grounded until test.
TVS and Zener-diode protected. |
DRY CONTACT
DETECTION RANGE |
Closed: <20 ohm, Open:> 5,000 ohm |
| RESISTOR DETECTION RANGE |
50 to 5,000 Ohm |
| TRIGGER INPUT VOLTAGE |
Open/Close: 30-300V dc or peak ac |
| VOLTAGE SENSING INPUT RANGE |
V1: analog input; 0-255V dc or peak ac, Sensitivity ±1V
V2: voltage detector (present/absent) input;
30-300V cd or peak ac |
| BREAKER OPERATION |
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open |
| BREAKER INITIATE CAPACITY |
30A/250V ac/dc max |
INITIATE CURRENT
READING RANGE |
One, Non-contact, Hall-Effect sensor, 0-20A, dc to 5Khz |
| TRAVEL TRANSDUCER INPUT |
3 digital travel transducer channel;
Linear range, 0.0-60.0 in (±0.01 in);
Rotary range 0-360° (±0.36°) |
CONTACT
TRAVEL POINT DIFFERENCE |
Measures “Slow-Close” contact-point distances (hard copy) |
| DISPLAY |
4 lines by 20 character back-lit LCD, sunlight viewable |
| PRINTOUT |
Both graphic contact and travel waveforms & tabulated results are printed on 4.5-inch thermal printer |
| TEST RECORD STORAGE |
Store up to 200 timing records |
| COMPUTER INTERFACES |
USB and RS-232C port |
| PC SOFTWARE |
Furnished Circuit breaker analysis software running under Windows XP; features graphic display,
numerical reports, and data base utility for use at shop or office. |
| SAFETY |
Designed to meet UL 6101A-1 Certification and CAN/CSA C22.2 No 1010.1-92 |
| ENVIRONMENT |
Operating: -10°C to 50°C (+15°F to +122°F);
Storage: -30°C to70°C (-22°F to +158°F) |
| OPTIONS |
Hard case for shipping; available for both Travel Transducers and CT-6500 |
| WARRANTY |
One-year warranty on parts and labor |